4 & 8 INPUT

The Addressable 4 or 8 Input Modules are fully monitored devices which permit the interfacing of third-party equipment with the fire alarm control panel using normally open dry contact connections.

The connection to each input is monitored for fault (open or short circuit) and alarm conditions.

The interface is used to monitor the contacts of an external system which must be interfaced to the fire alarm system, for example a flow switch in a sprinkler system to indicate if the sprinklers have been activated or extinguishant level monitoring in gas extinguishing systems, etc.

A 4-way DIL switch is provided to configure the module’s address. This value can be set in the range from 1 to 125.

 

TECHNICAL SPECIFICATIONS

SUPPLY VOLTAGE Loop Powered – 17 V to 30 V DC
LOOP CURRENT – QUIESCENT ( ) 4 Input 2.6 mA – 8 Input 3.2 mA
LOOP CURRENT – ALARM IQ+ 0.9 mA for each I/P in alarm
LOOP CURRENT – SHORT-CIRCUIT IQ+ 0.9 mA for each I/P in short-circuit
LOOP CURRENT – OPEN CIRCUIT IQ+ 0.5 mA for each I/P in open circuit
MAX. CABLE SIZE 2.5 mm²
CASE MATERIAL ABS
OPERATING TEMPERATURE -10ºC to 50ºC
MAX. HUMIDITY 95% RH Non-Condensing
DIMENSIONS 150 (W) x 90 (L) x 32 (H) mm
WEIGHT 4 Input 205 g / 8 Input 215 g – boxed

DOWNLOADS

This content has been restricted to logged in users only. Please login to view this content.