AQUAMASTER PLUS

The AQUAMASTER + is a single loop Analogue Addressable Water Leakage control panel which can be expanded to two loops. It provides a cost effective solution for small to medium sized installations. They can monitor up to 125 Signaline WDM-KM Control Modules per loop each of which controls up to 1000 m of Signaline Water Detection Cable.

Using Global Fire’s advanced communications mechanism, up to 32 individually addressed Loop sounders can be connected to each of the AQUAMASTER PLUS detection Loops. The AQUAMASTER PLUS also supports Shadow and Auxiliary Sounder/ Beacons together with GFE’s range of addressable Sounder/ Beacon along with all other GFE Interface devices.

The panel is equipped with a backlit LCD display of 4 rows each with 40 characters to give clear textual indications of Alarm/ Fault occurrences to the end user. There are also 16 Zone Alarm LED indicators.

AQUAMASTER PLUS Repeaters and Mini-Repeaters can be connected via an RS422/RS485, Fibre Optic or TCP/IP interface to facilitate remote display and control of the system.

An interactive graphic representation of the system can be displayed on the user’s computer via the ODYSSEY graphical software (optional). All the devices on the system can be displayed on a building plan showing their status in real time. In the event of alarm or fault the customer can control the system and access all the necessary information with a few mouse-clicks.

Automatic Device Detection at start up reduces time spent at the commissioning stage. In Installation mode the AQUAMASTER PLUS detects and recognises addressed and connected devices with the system being fully operational in less than two minutes.

The default programming ensures that the system is ready to detect Alarm/ Fault alerts from the moment that power is applied. Additional programming, to customise the system can be implemented using a laptop PC running the GFE CONNECTOR software which is available free of charge on GFE’s website.

TECHNICAL SPECIFICATIONS

PRIMARY SUPPLY VOLTAGE – INPUT 230 +10% -15% V AC
PRIMARY SUPPLY VOLTAGE – OUTPUT 28.5V DC nominal
PRIMARY SUPPLY CURRENT – OUTPUT 2.4 A @ 28.5V DC nominal (max.)
SECONDARY SUPPLY VOLTAGE 21.0 Min. – 27.2 Max.V DC -BAT charger o/p 28V DC
SECONDARY SUPPLY CURRENT OUTPUT 1.6 Amp Maximum @ 200C
INTERNAL BATTERY CAPACITY – MAXIMUM 2 x 12 V 7Ah Sealed VRLA Lead Acid Batteries
LOOP CURRENT DRIVE 275 mA/Loop
AUXILIARY RELAY OUTPUTS 2 Alarm (COM-NC-NO) – 1 Fault (COM-NC) non-supervised
CONVENTIONAL SOUNDER CIRCUITS 2 – 400 mA Max. current drive per circuit – Fully monitored
MAX. HUMIDITY 95% RH Non-Condensing
OPERATING TEMPERATURE -10ºC to 50ºC
WEIGHT 2.0 Kg – 7 Kg (inc. 2 x 7 Ah 12 V bat.)
DIMENSIONS 272 (W) x 404 (H) x 107 (D) mm
COLOUR White or Red