BCM 3

This unit is a fully EN-54 Part 4 compliant battery charger.

It can be supplied as a standalone module or boxed in an ABS plastic enclosure, including a 28V DC @ 1.7 or 2.4 Amp PSU. The standalone unit has 10A current rating and is supplied complete with heat dissipation.

TECHNICAL SPECIFICATIONS

SUPPLY INPUT 230 +10% -15% V AC – Monitored
SUPPLY OUTPUT 1.7 A OR 2.4 A @ 28V DC nominal
BATTERY CHARGER – CURRENT O/P 1 A max.
BATTERY TYPE / FUSE Max. 2 x 12 V 7 AH – Lead Acid VRLA / 3 A
I/O UNIT – LOOP CURRENT 1.7 mA Quiescent – 2.4 mA Fault
FAULT RELAY Changeover – 30V DC 1 A Resistive
I/O CONTROLLED RELAY Changeover – 240 V AC 10 A Resistive
OPERATING TEMPERATURE -10ºC to +50ºC
HUMIDITY / PROTECTION Max. 95% no condensation / IP21
DIMENSIONS 273 (L) x 107 (W) x 404 (H) mm
WEIGHT 1.7 Kg – 7 Kg inc. 2 x 7 AH Bat.