BCM-5 & BCM-10
This unit is a fully EN54-4 compliant PSU incorporating a battery charger that can be used with all GFE addressable fire detection panels. It will monitor all fault conditions including charger fault, charger voltage level, input voltage supply fault and supply removal. It is supplied boxed in an aluminium enclosure, including a 28V DC @ 5.6A or 11.7A PSU.
DOWNLOADS
SUPPLY INPUT | 230 +10% -15% V AC – Monitored |
SUPPLY OUTPUT | 5.6A or 11.7A @ 28V DC nominal |
BATTERY CHARGER – CURRENT O/P | 4A max. |
BATTERY TYPE | Max. 2x 12V 7AH – Lead Acid VRLA |
BATTERY FUSE | 5A / 10A |
I/O UNIT – LOOP CURRENT | 1.7mA Quiescent – 1.8mA Fault |
FAULT RELAY | Changeover – 30V DC 1A Resistive |
I/O CONTROLLED RELAY | Changeover – 240V AC 10A Resistive |
OPERATING TEMPERATURE | -10ºC to +50ºC |
HUMIDITY / PROTECTION | Max. 95% no condensation / IP21 |
DIMENSIONS | 345 (L) x 375 (W) x 139 (W) mm |
WEIGHT | 3.5Kg – 11.5Kg inc. 2 x 12AH Bat. / 4Kg – 12kg inc. 2 x 12AH Bat. |
DOWNLOADS