GEKKO

The GEKKO Fire Alarm Control Panel is the successor to GFE’s well-known JUNIOR V4 panel.

The GEKKO can have from 1 to 4 addressable loops. It is housed in a functional ABS plastic enclosure, with only two screws used to close and secure the lid.

The new graphic backlit LCD display can accommodate any type of custom characters or graphic symbols, allowing multi-language support, as well as visual and customisable elements.

It can communicate with our proprietary ODYSSEY Graphics Interface, as well as with third party Building Management Systems through a Modbus output. It is also capable of communicating with a repeater unit, using any of the networking interfaces of the CHAMELEON protocol.

Inside the cabinet there is space to install up to 7 AH 24V DC Sealed Lead Acid backup batteries, providing battery supply to the GEKKO and ZEOS associated devices, which boast extremely low energy consumption.

The Cause and Effect programming, as well as all customer specific configuration, is introduced in the GEKKO using the CHAMELEON CONNECTOR software, which is then downloaded to the flash memory of the unit.

TECHNICAL SPECIFICATIONS

MAINS POWER SUPPLY RATING90V AC to 230V AC
PRIMARY DC SUPPLY28.5V DC @ 2.4 A (Max)
SECONDARY SUPPLY21.6 Min. – 27.2V DC (Max) – Battery charger: 27.5V DC
BATTERY CAPACITY (INTERNAL)Small box maximum capacity 2x 12 V 9 AH; Large box max. capacity 2x 12 V 12 AH
QUIESCENT CURRENT (NO DEVICES)60 mA
AUX POWER OUTPUT2 x 24V DC 300mA / 1 x 24V switched out
MAXIMUM LOOP OUTPUT CURRENT1 – 4 loops 900mA alarm peak/165mA quiescent per loop
LOOP TOPOLOGYClass A (loop) or Class B (radial)
LOOP CABLEFire resistant 2 x 1.5mm (max 1200m) or 2 x 2.5mm (max 2000m)
CONVENTIONAL SOUNDER CIRCUITS500mA for conventional sounder circuits a+b
AUX. RELAYS FIRE2 x rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive
AUX. RELAY FAULT1 rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive
GRAPHICAL LCD DISPLAYHigh definition, high contrast blue backlit 240 x 64 pixels
COMMUNICATION CHANNELS2 x configurable communications ports
BMS OUTPUTODYSSEY (Graphical software), TCP IP-WEB (remote web monitoring), MODBUS RTU, ESPA 4.4.4
SOFTWARE CONNECTIONUSB type B
EVENT LOG10,000 events
OPERATING / STORAGE TEMPERATURE-10ºC to 50ºC
HUMIDITYMax. 85% RH Non-Condensing
INGRESS PROTECTIONSurface Mount: IP30, Recessed Mount: IP65
DIMENSIONSStandard box: 273 (L) x 403 (H) x 106 (W) mm / Deep box: 273 (L) x 403 (H) x 142 (W) mm
WEIGHT1.6 Kg (no batteries)
ENCLOSURE COLOURSWhite (RAL 9003) and Red (RAL 3001)