GFE AD ISO

The GFE-AD-ISO is a standalone negative switching loop isolator designed to isolate short circuits on the addressable detection loop of all GFE addressable fire alarm control panels.

Up to 32 detection devices may be connected between two isolators as per EN54.

The GFE-AD-ISO is loop powered and polarity sensitive and care must be taken to follow the indications on the PCB. Also, as two LEDs are fitted to facilitate ‘Loop in’ and ‘Loop out’ identification, a consistent approach should be taken when wiring the isolator.

TECHNICAL SPECIFICATIONS

LOOP OPERATING VOLTAGE 17 V to 40 V
LOOP CURRENT – QUIESCENT 0.25 mA @ 28 V DC nominal
LOOP CURRENT – ISOLATED LED ON 6.2 mA @ 28 V DC nominal
MAXIMUM SERIES IMPEDANCE (Zcmax) 28 mOhm
MAX LEAKAGE CURRENT (iLmax) 2.7 mA
MAX RATED SWITCHING CURRENT (ls max) 1 A
MAX. CABLE SIZE 2.5 mm²
OPERATING TEMPERATURE -10ºC to 50ºC
MAX. HUMIDITY 95% RH Non-Condensing
ENCLOSURE / MATERIAL White or Red / ABS
DIMENSIONS 100 (D) x 48 (H) mm
WEIGHT 105 g – 142 g including packaging