GFE DHA V2

Loop powered addressable magnetic door holder. It does not require external supply as it is directly powered by the loop. The activation of the unit is achieved using cause and effect programming as used for I/O units.

The module is fitted with 3 status LEDs. The Green LED will flash slowly when the battery is charged, and flash faster when the battery is in charge mode. The presence of this LED also indicates that the device is polled by the addressable panel. The Yellow LED indicates that the isolator is active (short circuit in the loop cables). 

The  combination between the Green and Red led returns several status informations decoded in a table.

The activation of the module can be achieved as part of the cause and effect programming of the panel and it operates in the same way as an I/O unit. This unit should normally be assigned to either a specific device or zone. Up to a maximum of 20 of these units can be fitted on a particular loop.

TECHNICAL SPECIFICATIONS

SUPPLY VOLTAGE Loop Powered – 17V DC to 30V DC
ADDRESS RANGE 1-125
LOOP CURRENT – QUIESCENT / CHARGING 800 uA (650 uA module + 150 uA isolator) / 7 mA
ISOLATOR – LOOP LINE RESISTANCE 60 mOhms
SLEEP MODE CONSUMPTION 28 ~ 60 uA
CHARGE UP TIME / FAIL SAFE RELEASE TIME (1) 25s / 30s
MANUAL RELEASE Push Button – Normally Open
MAX. CABLE SIZE 2.5 mm2
MAX. HUMIDITY 95% RH Non-Condensing
OPERATING TEMPERATURE 0ºC to 50ºC
MAGNETIC FORCE 200 N
DIMENSIONS (MAGNET) 112.5 (H) x 84.2 (W) x 46.8 (D) mm
DIMENSIONS (KEEPER) 55 (H) x 55 (W) x 50 (D) mm
WEIGHT (KEEPER) 139 g
WEIGHT (MAGNET WITH MODULE) 580 g
WEIGHT (COMPLETE BOXED) 746 g

1) Fail Safe Release Time is defined as the time taken to release the door after removal of loop power or loss of communication
with the control panel is detected.