J-NET MPX REL
J-NET MPX REL is an interface card that provides zone in Fire/Fault indication via a voltage free change-over relay contact for each zone in any of GFE’s analogue addressable fire detection panels. There is also a LED indication of FIRE/FAULT condition for each individual zone. The LED red indicator will be ON when the relay is active. These relay outputs are not monitored.
The module requires an external 24 V DC supply and connection to either JUNO NET or JUNIOR panels is via a 5-way flat cable fitted with polarised connectors. Two of these connectors are provided to enable connection of more than one module. This module operates in three different modes.
TECHNICAL SPECIFICATIONS
SUPPLY VOLTAGE | 28V DC nominal |
LOOP CURRENT – QUIESCENT | 7 mA – No relays active |
CURRENT – ZONES IN ALARM | 7 mA + 15 mA per active relay |
ZONE SELECTION | DIL Switch |
OPERATING TEMPERATURE | -10ºC to 50ºC |
MAX. HUMIDITY | 95% RH Non-Condensing |
DIMENSIONS | 88 (L) x 72.5 (W) x 18 (H) mm |
WEIGHT | 4 Zone: 60 g / 8 Zone: 95 g |