JUNO NET REP
The Juno Net Repeater Panel, J-NET-EN54-REP, fully replicates the control panel information and control facilities allowing multiple operating points within the system. The J-NET-EN54-REP communicates with the Master Control Panel via an RS422/RS485, Fibre Optic or TCP/IP network. Sub-Panels can be integrated into the repeater panel to allow the connection of up to three additional detection loops per sub-panel to the system.
J-NET-EN54-REP is ideal for multiple building complexes where display and control of the system is required in various locations. Depending on control panel loading, power for the J-NET-EN54-REP can be supplied from the control panel’s auxiliary power output, an external 24V power supply or an optional complete built-in 24V, 2,4A or 5A power supply unit. If a sub-panel is installed in the repeater housing, then a 5A power supply unit is required.
TECHNICAL SPECIFICATIONS
NO LOOP CARD | WITH LOOP CARD | |
LOOPS | N/A | 1, 2 or 3 loops – Max. 275 mA per loop |
SOUNDER OUTPUTS | 2 – 28 V DC / 500 mA each | 2 – 28 V DC / 500 mA each |
AUX. RELAYS FIRE | 2 rated 50 VAC / DC 1A resistive | 2 rated 50 VAC / DC 1A resistive |
AUX. RELAY FAULT | 1 rated 50 VAC / DC 1A resistive | 1 rated 50 VAC / DC 1A resistive |
AUX SUPPLY OUTPUT | 28 V DC; 2×230 mA | 28 V DC; 2×230 mA |
ADDITIONAL OUTPUTS | Multiplexed up to 384 Zones | Multiplexed up to 384 Zones |
PRIMARY SUPPLY | N/A | 230 +10% -15% V AC |
SECONDARY SUPPLY | 28 V DC Nominal | 28 V DC Nominal |
POWER SUPPLY RATING | N/A | 65 W |
QUIESCENT CURRENT (NO DEVICES) | 110 mA | 130 mA no loop devices fitted |
BATTERIES (INTERNAL) | 2 x 12 V 12 AH | 2 x 12 V 12 AH |
OPERATING TEMPERATURE | -10ºC to 50ºC | -10ºC to 50ºC |
STORAGE TEMPERATURE | -10ºC to 50ºC | -10ºC to 50ºC |
HUMIDITY | Max 95% no condensation | Max 95% no condensation |
PROTECTION | IP21 | IP21 |
DIMENSIONS | 375 (L) x 345 (W) x 139 (H) mm | 375 (L) x 345 (W) x 139 (H) mm |
WEIGHT | 4,5 Kg (no batteries) | 5,1 Kg (no batteries) |
COLOUR | White or Red | White or Red |