NODE

The NODE allows expansion of the JUNO NET system in groups of 1 to 4 loops.

It can be supplied as a standalone unit or in an enclosed cabinet, which contains a 2,3 A PSU/ Charger unit and space for standby rechargeable batteries. One RS422/RS485, fibre optic or TCP/IP interface is required per cabinet to enable networking with the rest of the system.

Each NODE mainboard controls up to four analogue addressable detection loops via its own independent processor. In the event of communication failure with the main control unit, the NODE can operate independently, detecting Fire/Fault events and activating connected sounders and internal relays.

TECHNICAL SPECIFICATIONS

PRIMARY SUPPLY 2.3A @ 28.5V DC nominal
POWER SUPPLY RATING 65 W
SECONDARY SUPPLY 28V DC nominal
BATTERIES N/A
QUIESCENT CURRENT (NO DEVICES) 80 mA
AUX POWER OUTPUT 28V DC 300 mA
LOOPS 1 to 4 – max 275 mA/ Loop
CONVENTIONAL SOUNDER CIRCUITS 1A max current drive for both circuits – Fully monitored
AUX. RELAYS FIRE/ sub-panel 2x SPDT; rated 2A @ 30V DC resistive / 0.25A @ 230V AC resistive
AUX. RELAY FAULT/ sub-panel 1x NC; rated 2A @ 30V DC resistive / 0.25A @ 230V AC resistive
OPERATING TEMPERATURE 0°C to +50°C
STORAGE TEMPERATURE -10°C to +50°C
DIMENSIONS 113 (L) x 187 (W) x 26 (H) mm
WEIGHT (NO BATTERIES) 0.3 Kg