ORION-PLUS

The ORION + range of expandable conventional control panels offers an aesthetically pleasing and functional cabinet design for larger projects demanding ease of installation and commissioning, as well as simple operation, such as conventional installations.

The unit can be expanded easily from eight to 16 zones by installing additional modules with four zones. The range also includes two types of repeater.

The outstanding programming features included in this panel range exceed the possibilities of standard conventional panels, using a graphic LCD display and real time clock which permits the recording of events in a time stamped log.

Operation is intuitive, offering simple control and one-button disablement facilities, as well as a one-man test routine, which provides a highly effective way to perform regular testing of the fire alarm system.

Advanced configuration interfacing includes RS232, RS422/485, fibre optic, GSM-GPRS and TCP/IP. All of the above make use of our own proprietary interfaces.

TECHNICAL SPECIFICATIONS

PRIMARY SUPPLY VOLTAGE – IN90 to 265 V AC
PRIMARY SUPPLY VOLTAGE – OUT28.5 V DC nominal
PRIMARY SUPPLY CURRENT – OUT1.7 A @ 28.5 V DC nominal (max.)
SECONDARY SUPPLY VOLTAGE21.0 min. – 27.2 max. V DC – BAT charger o/p 28 V DC
SECONDARY SUPPLY CURRENT OUTPUT1.1 Amp Maximum @ 20ºC
INTERNAL BATTERY CAPACITY – MAXIMUM2 x 12 V x 7 Ah Sealed VRLA Lead Acid Batteries
MAINS FUSE4 A -250 V Slow Blow – 20 mm
BATTERY FUSE1.6 Amp – Resettable
NUMBER OF CIRCUITS16 Max.
ZONE CURRENT – QUIESCENT / ALARM4 mA / 60 mA – Maximum
MAX. CABLE RESISTANCE / CAPACITANCE40 Ohms / 0.470 uF
END OF LINE MONITORINGActive EOL – 10uF/50V Bipolar Electrolytic Aluminium Capacitor
BS-5839 DETECTOR REMOVAL COMPLIANTYES (provided diodes are fitted to detector base)
DEVICES PER ZONE32 Maximum – EN54 pt.2
ALARM RESISTANCE VALUE270 – 1000 Ohms
CURRENT OUTPUT2 outputs w/ 500 mA max. current drive per circuit – fully monitored
ALARM VOLTAGE / END OF LINE RESISTOR27.5 V DC Nominal / 10 K Ohms – 1/4 Watt
AUXILIARY RELAY OUTPUT1 Fire (COM-NC-NO) – 1 Fault (COM-NC) non-supervised
RELAY CONTACT RATING50 V DC – 1 Amp resistive loads
PROGRAMMABLE INPUT 1 / INPUT 2Non-Latching – Voltage free contact / Non-Latching – Voltage free contact
HUMIDITYMax 95% RH Non-Condensing
OPERATING TEMPERATURE-10ºC to 50ºC
WEIGHT (ORION-PLUS)2 Kg without batteries, 7 Kg with batteries (2 x 12 V x 7Ah)
DIMENSIONS (ORION-PLUS)273 (L) x 107 (W) x 404 (H) mm
COLOURWhite or Red